| Model: 934324 |
 |
Optional Sensor
Analog control 0-10 VDC
High Temperature Sensor
|
|
.
- Voltage and Current Converter/Rescaler
will convert voltage signals in the range of 1-19V or current
signals in the range of 1.33-76 mA into a 4-20 mA non-isolated
signal. This current source signal can be direct or reverse acting
and can be used to drive grounded 4-20 mA loads utilizing a single
power supply. Also accepts an input from a resistive potentiometer.
The unit is a single-input, single-output device
| FEATURES |
- Converts voltage, current
or potentiometer signal into 4-20 mA signal
- Direct or reverse acting
- 6 or 10 VDC output
reference voltage available to power input device
- Loss of input signal
results in zero mA output
- LED indication of valid
input signal
- Dual output model
available
- Outputs independently
configurable
|
|
SPECIFICATIONS |
| |
Power supply |
22-27 VDC @ 50 mA (10V ref.
voltage output); 15-27 VDC |
| |
|
@ 50 mA (6V ref. voltage
output) |
| |
Input ranges |
1-19 VDC, 1 V min span, |
| |
|
301 kohm input impedance |
| |
|
150 kohm input impedance |
| |
|
4-76 mA, 4 mA min span, |
| |
|
250ohm input impedance |
| |
|
2-38 mA, 2 mA min span, |
| |
|
500ohm input impedance |
| |
|
1.33-25 mA, 1.33 mA min span, |
| |
|
750ohm input impedance |
| |
Input signal
loss |
| |
threshold |
0.7 VDC |
| |
Output range |
4-20 mA |
| |
Output load |
850ohm max 24 VDC; Rmax =
Vsupply- 7 / 20 mA |
| |
Reference voltage output |
10 VDC 15 mA max (1-19 VDC
input); 6 VDC 10 mA max (1-11 VDC input) |
| |
Linearity |
1.0% of span |
| |
Operating temp |
32° to 158°F (0° to 70°C) |
| |
Humidity limit |
5% to 95% non condensing |
| |
Mounting |
Snap-track 1/2" hub,
panel, or DIN rail mount enclosures |
| |
Terminations |
Snap-track mount: screw
terminals; |
| |
Weight |
2 oz. (69 g) |
| |
Dimensions |
2.25" W x 1.75" H x 0.8"D
(5.72 x 4.45 x 2.22 cm) |
- Made in USA
|
|
| |
|